Control Description The Boiler Control 265 is a microprocessor-based control designed to operate up to three modulating boilers. The 265 can provide either outdoor reset and setpoint operation or outdoor reset and DHW operation. The 265 provides either sequential or parallel modulation and has Equal Run Time Rotation of the boilers. The control also operates the system pump and individual boiler pumps. The 265 provides either a 0 -20 mA or 4 -20 mA signal to each boiler. A contact is also available for either a combustion air damper or external alarm. The control can provide outdoor reset using an outdoor sensor or the control can accept a 0 -10 V (dc) signal from an EMS / BAS to establish the required water temperature.
Literature |
|
|
Control |
|
Microprocessor PID control; This is not a safety (limit) control |
Packaged Weight |
|
3.5 lb. (1600 g), Enclosure A, blue modified PVC plastic |
Dimensions |
|
6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
Approvals |
|
CSA C US, meets ICES & FCC regulations for EMI/RFI |
Ambient Conditions |
|
Indoor use only, 32 to 104°F (0 to 40°C), < 90% RH non-condensing |
Power Supply |
|
115 V (ac) ±10% 50/60 Hz 600 VA |
Relays |
|
230 V (ac) 5 A, 1/3 hp, pilot duty 230 VA |
Modular Output |
|
0-20 mA / 4-20 mA (up to 1000Ω load) |
Demands |
|
20 to 260 V (ac) 2 VA |
Sensors Included |
|
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
|
Quick 002 003 004 005 007 011 024 031 032 033 039 040 060 062 070 071 072 073 076 077 078 079 080 081 082 083 084 085 090 092 132 150 152 153 155 156 157 161 162 256 257 260 261 262 263 264 265 268 269 270 274 275 279 313 314 315 316 324 325 326 334 335 336 337 345 346 356 360 361 362 363 364 365 369 374 400 401 402 420 421 422 423 440 441 444 479 480 481 482 483 507 508 509 510 511 512 527 528 530 537 538 540 541 542 543 544 545 546 650 664 665 667 704 710 720 741 |
Copyright ©2010 tekmar Control Systems Ltd. |