Control Description The Universal Reset Control 363 is a microprocessor-based control capable of providing both a reset boiler supply temperature and a reset mixed supply temperature based on outdoor air temperature. For a mixing device, the 363 can use either a variable speed injection pump or a floating action mixing valve. The 363 is also capable of controlling an indirect Domestic Hot Water (DHW) storage tank and / or a setpoint load. Individual zone temperature control can be achieved by using either a conventional thermostat system, or by connecting a tekmar Zone Control(s) to the 363.
Literature |
|
D 363, A 363's, D 001, D 070, E 003, E 021, U 363 |
Control |
|
Microprocessor PID control; This is not a safety (limit) control |
Packaged Weight |
|
3.9 lb. (1760 g), Enclosure A, blue PVC plastic |
Dimensions |
|
6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
Approvals |
|
CSA C US, meets ICES & FCC regulations for EMI/RFI |
Ambient Conditions |
|
Indoor use only, 32 to 122°F (0 to 50°C), <95%RH non-condensing |
Power Supply |
|
120 V ±10% 50/60 Hz 1800 VA |
Variable Pump |
|
240 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250 V |
Relays |
|
240 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA |
Demand |
|
20 to 260 V (ac) 2 VA |
Sensors Included |
|
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
Optional Devices |
|
tekmar type #: 011, 031, 032, 040, 062, 063, 071, 072, 073, 076, 077, 078, 079, 367, 368, 369 |
|
Quick 002 003 004 005 007 011 024 031 032 033 039 040 060 062 070 071 072 073 076 077 078 079 080 081 082 083 084 090 092 132 150 152 153 155 156 157 161 162 256 257 260 261 262 263 264 265 268 269 270 275 279 325 326 335 336 337 345 346 356 360 361 362 363 364 365 369 374 420 421 422 423 440 441 444 479 480 481 483 507 508 509 510 511 512 537 538 540 541 542 543 544 545 546 650 664 665 667 704 710 720 741 |