Search tekmarcontrols.com

arrow Snow Melting Control 650 - Pulse Width Modulation

tekmar Snow Melting Control 650

Control Description The Snow Melting Control 650 is a microprocessor-based manual start / stop control that maintains a set temperature in a snow melting slab. The 650 uses pulse width modulation (PWM) to operate an on / off injection valve, pump, boiler or contactor for electric cables. Other 650 features include Slab Outdoor Reset, Warm Weather Cut Off, Cold Weather Cut Off, Snow Melting Setpoint and Snow Idling Setpoint. The control also has a built-in timer for timed melting events.

 

Literature

D 650, A 650's, D 001, D 070, D 079

Control

Microprocessor PI control; This is not a safety (limit) control

Packaged Weight

1.3 lb. (600 g), Enclosure C, white PVC plastic

Dimensions

4-3/4" H x 2-7/8" W x 7/8" D (120 x 74 x 22 mm)

Approvals

CSA C US, meets ICES & FCC regulations for EMI/RFI

Ambient Conditions

Indoor use only, -20 to 120°F (-30 to 50°C), < 90% RH non-condensing

Power Supply

Class 2, 24 V (ac) ±10% 50/60 Hz 2 VA or 32 V (dc) ±20% 0.04 A

Relays

240 V (ac) 10 A 1/3 hp, pilot duty 240 VA 2 A

Sensors Included

NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
Outdoor Sensor 070 and Slab Sensor 072

On Time

0:30 to 19:50 hours to 'Infinite'

Melting

34 to 45°F (1 to 7°C)

Idling

Off, 23 to 34°F (Off, -5 to 1vC)

CWCO

Off, -22 to 23°F (Off, -30 to -5°C)

Temperature Display

Fahrenheit / Celsius

 

 


Quick
links:

002 003 004 005 007 011 024 031 032 033 039 040 060 062 070 071 072 073 076 077 078 079 080 081 082 083 084 090 092 132 150 152 153 155 156 157 161 162 256 257 260 261 262 263 264 265 268 269 270 275 279 325 326 335 336 337 345 346 356 360 361 362 363 364 365 369 374 420 421 422 423 440 441 444 479 480 481 483 507 508 509 510 511 512 537 538 540 541 542 543 544 545 546 650 664 665 667 704 710 720 741