The Relay 004 is a 120 V (ac) coil DPDT (double pole double throw) relay that is used to isolate electrical loads and allow higher current ratings than the on board relays found on tekmar controls. It can be used in applications ranging from doubling the capability of a single output (e.g. energize a pump as well as provide a boiler demand from one output) to allowing a pump to be used that draws more than the control s specified relay rating. The 004 relay uses a 120 V (ac) coil that once energized, closes 2 normally open contacts, and opens 2 normally closed contacts.
Double Pole Double Throw relay (DPDT)
Easy to replace ("ice cube" style - no need to remove wiring)
Isolate electrical loads
LED to indicate when energized
Test tab for easy test and manual override
| Packaged weight | 0.4 lb (180 g) |
| Dimensions | 3" H x 1-9/16" W x 2-3/8" D (75 x 40 x 60 mm) |
| Approvals | CSA C US |
| Power supply (coil) | 120 V (ac) +10%, -20%, 50 Hz 2.7 VA, 60 HZ 2.3 VA |
| Relay contacts (max.) | 10 A resistive @ 250 V (ac) N.O., N.C. |
| 10 A resistive @ 30 V (dc) N.O., N.C. | |
| 7 A inductive @ 250 V (ac) | |
| Relay contacts (min.) | 10 mA 1 V (dc) |
| Ambient conditions | Indoor use only, -40 to 140°F (-40 to 60°C), RH < 85% Non-condensing |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
May 2011 - Present |
|
Installation & Operation Manual |
Sep 2009 - Mar 2011 (for 004 s with LED light and test button) |
|
|
Installation & Operation Manual |
May 2007 - Sep 2009 (for 004 s without LED light) |
|
|
Installation & Operation Manual |
Jan 2005 - May 2007 |
|
|
Installation & Operation Manual |
Jan 2010 - Present |