The Boiler Control 261 is designed to stage two on/off boilers using Outdoor Temperature Reset. It can be used in applications ranging from a single zone of baseboard, multiple baseboard and fan coil zones, to dedicated setpoint heating in commercial buildings. This control regulates a single heating water temperature through Outdoor Temperature Reset and/or setpoint target control. It is capable of controlling (stage and rotate) up to 2 on/off boilers, or a single 2 stage boiler, as well as the system pump.
2 Stage boiler control
Advanced settings to fine-tune building requirements
Automatic Boiler Differential
Exercising
Outdoor Temperature Reset
Powered boiler pump output
Quick setup for easy installation and programming of control
Setback input for energy savings
Test sequence to ensure proper component operation
User comfort adjustment to increase or decrease building space temperature
Warm Weather Shut Down
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.0 lb. (1340 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA C US, meets class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 113°F (0 to 45°C), RH ≤90% Non-condensing |
| Power supply | 120 V (ac) ±10%, 50/60 Hz, 1300 VA |
| Relays | 240 V (ac) 10 A, 1/3 hp |
| Demands | 20 to 260 V (ac) 2 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and Universal Sensor 082 |
| -Optional | tekmar type #: 071, 082 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Mar 2009 - Present |
Application Brochure |
Mar 2009 - Current |
More advanced application drawings can be found in our Solutions section.