The Boiler Control 270 is designed to operate a single modulating boiler using Outdoor Temperature Reset. It can be used in applications ranging from baseboard or radiant heating systems, to combination radiant and DHW systems. This control regulates a single heating water temperature through Outdoor Temperature Reset and/or setpoint/DHW control. It is capable of controlling a single modulating boiler, as well as the system pump.
Advanced settings to fine-tune building requirements
Boiler pump operation (optional)
DHW priority (optional)
DHW pump or valve operation
Exercising
Indoor Temperature Feedback
Modulating boiler control
Outdoor Temperature Reset
Powered system pump output
Quick setup for easy installation and programming of control
Setback input for energy savings
Test sequence to ensure proper component operation
User comfort adjustment to increase or decrease building space temperature
Warm Weather Shut Down
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.3 lb. (1500 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA C US, meets class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Non-condensing, Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree 2 |
| Power supply | 115 V (ac) ±10%, 50/60 Hz, 600 VA max |
| Relay | 230 V (ac) 5 A, 1/3 hp, pilot duty 240 VA |
| Modulation output | 0-10 V (dc) |
| Demands | 20 to 260 V (ac) 2 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and Universal Sensor 082 |
| -Optional | tekmar type #: 033, 076, 077, 084 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Aug 2010 - Present |
Application Brochure |
Aug 2010 - Current |
More advanced application drawings can be found in our Solutions section.
RF Noise Interference |
May 2009 - Present |
Modulating Boiler Interface Revision 8 |
Mar 2011 - Mar 2011 (Updated March 2011) |