The Steam Control 279 is designed to operate a single steam boiler using Outdoor Temperature Reset. It can be used in single pipe steam applications as well as applications using a tankless DHW coil. This control regulates the on time of a steam boiler through Outdoor Temperature Reset control. It is capable of controlling a single on/off steam boiler.
24 hour, 5-1-1, 7 day schedule
Built-in programmable timer
CSA approved for use in USA and Canada
DHW tankless coil operation
Indoor Temperature Feedback (with optional indoor sensor)
Large LCD display
Manual Override
Outdoor Temperature Reset
Two alert level relays
Two or four schedule events per day
Warm Weather Shut Down
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.3 lb. (1500 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA C US, meets Class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Non-condensing, Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree 2 |
| Power supply | 115 V (ac) ± 10%, 50/60 Hz, 3.5 VA |
| Relays | 230 V (ac) 5 A, 1/3 hp, pilot duty 240 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and Universal Sensor 071 |
| -Optional | tekmar type #: 071, 076, 077, 078, 082, 084 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
May 2010 - Present |
Application Brochure |
May 2010 - Current |
More advanced application drawings can be found in our Solutions section.
RF Noise Interference |
May 2009 - Present |