The Power Manager 345 is designed to provide power and mounting for a tekmarNet® 4 Reset Module. It can be used in applications that use Wiring Centers, or other zoning devices that require a single thermostat. This product provides a mounting enclosure, power for a tekmarNet® 4 Reset Module, and connects to one tekmarNet® 4 thermostat to control one zone pump.
CSA C US Certified for use in USA and Canada
Internal 56 VA transformer
Powered 115 V auxiliary pump output
tekmarNet® 4 compatible
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.5 lbs (1610 g) |
| Dimensions | 8-1/16" H x 11-1/8" W x 2-15/16" D (204 x 282 x 74 mm) |
| Enclosure | Blue PC+ABS plastic with metal top and bottom conduit connection walls, NEMA type 1 |
| Approvals | CSA C US, meets Class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤80% to 88°F (31°C), down to 50% above 104°F (40°C), Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree |
| Power supply | 115 V (ac) +/- 10%, 60 Hz, 12 A |
| Transformer power available | 24 V (ac) 56 VA, fuse T2.5 A 250 V |
| Auxiliary pump input | 24 V (ac) < 0.5 VA |
| Auxiliary pump relay | 115 V (ac) 5 A |
| Combined load | 11.5 A max |
| Warranty | Limited 3 Year Warranty |