The Mixing Control 361 is designed to operate a mixing pump using Outdoor Temperature Reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for Boiler Return Protection with full reset. This control regulates a single heating water temperature through Mixing Outdoor Reset. It provides mixing by speeding up or slowing down a single permanent capacitor (standard wet rotor) circulator, and provides control of the mix system pump.
Advanced settings to fine-tune building requirements
Automatic Boiler Differential
Boiler Load control
CSA C US certified (approved to applicable UL standards)
Indoor Temperature Feedback (with optional indoor sensor)
Outdoor Temperature Reset
Powered mixing system pump output
Quick setup for easy installation and programming of control
Setback input for energy savings
Test sequence to ensure proper component operation
User comfort adjustment to increase or decrease building space temperature
Variable speed pump control
Warm Weather Shut Down
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.0 lb. (1380 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA C US, meets class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Non-condensing |
| Power supply | 120 V (ac) ±10%, 50/60 Hz, 1650 VA |
| Variable pump | 120 V (ac) 2.4 A (FLA) 5 A (LRA) fuse T2.5 A 250 V |
| Relays | 240 V (ac) 10 A 1/3 hp |
| Demand | 20 to 260 V (ac) 2 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and 2 of Universal Sensor 082 |
| -Optional | tekmar type #: 033, 076, 077, 084 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Mar 2009 - Present |
Application Brochure |
Mar 2009 - Current |
More advanced application drawings can be found in our Solutions section.
RF Noise Interference |
May 2009 - Present |