The Mixing Control 365 is designed to operate a mixing device using Outdoor Temperature Reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for boiler protection with full reset. This control regulates a single heating water temperature through outdoor reset. It provides mixing by using a 4-20 mA output to control an analog mixing device such as a mixing valve or variable frequency drive, or a variable speed output to a 120 V pump. It can also control the mix system pump.
4-20 mA mixing output
Automatic Boiler Differential
Boiler Load Reset
CSA C US certified (approved to applicable UL standards)
Indoor Temperature Feedback (optional)
Outdoor Temperature Reset
Powered mixing system pump output
Quick setup for easy installation and programming of control
Setback input for energy savings
Test sequence to ensure proper component operation
User comfort adjustment to increase or decrease building space temperature Advanced settings to fine-tune building requirements
Warm Weather Shut Down
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.3 lb. (1500 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA, UL listed, meets ICES & FCC regulations for EMI/RFI. |
| Ambient conditions | Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Non-condensing |
| Power supply | 120 V (ac) ±10% 50/60 Hz 300 VA |
| System Pump | 120 V (ac) 12 A 1/3 hp, pilot duty 480 VA 4 A |
| Variable Pump | 120 V (ac) 50/60 Hz 2.2 A 1/6 hp, internally fused |
| Boiler Relay | 120 V (ac) 10 A 1/4 hp, pilot duty 240 VA 2 A |
| Demands | 24 to 120 V (ac) 2 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and Universal Sensor 071. |
| -Optional | tekmar type #: 033, 071, 072, 073, 076, 077, 082, 084 |
| Warranty | Limited 3 Year Warranty |