The Boiler Reset Module 420 is designed to operate all of the mechanical equipment in a hydronic heating system, except for zones, coordinating their operation through network communication. It can be used in applications ranging from a single zone of baseboard with an on/off boiler, to multiple radiant floor zones with a modulating/condensing boiler. This control regulates one space heating water temperature through Outdoor Temperature Reset and Indoor Temperature Feedback. It is capable of controlling a single on/off or modulating boiler, Domestic Hot Water, setpoint loads, and can expand up to 24 zones in total.
Automatic Boiler Differential
Boiler Protection
DHW Post Purge
DHW Priority (optional)
DHW control
Exercising
Indoor Temperature Feedback
One touch overrides (with optional User Switch)
Outdoor Temperature Reset
Powered pump outputs
Setpoint operation
Single on/off, or modulating boiler control
System Setback (with optional Timer)
System control for up to 24 zones
Warm Weather Shut Down
Zone Synchronization
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 1.6 lb. (730 g) |
| Dimensions | 3-5/8" H x 5-3/8" W x 9/16" D (92 x 137 x 14 mm) |
| Approvals | CSA C US, meets Class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤80% to 88°F (31°C), down to 50% above 104°F (40°C), Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree |
| Power supply | Provided by interconnected tekmarNet Zone Manager |
| Pump relays | 115 V (ac) 5 A, 1/6 hp |
| Combined load | 10 A max (for DHW and Primary Pump) |
| DHW zone valve | 24 V (ac) 8 VA max |
| Modulation output | 0-10 V (dc) minimum 2500 Ω |
| Boiler relay | 115 V (ac) 5 A, 1/6 hp |
| Demands | 20 to 260 V (ac) / 0.1 VA @ 24 V |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and Universal Sensor 082 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Aug 2007 - Present |
|
|
Job Record |
Aug 2009 - Present |
|
|
Wiring Brochure |
Mar 2009 - Present |
Installing tN4 Reset Modules 420, 422 and 423 with Modulating Boilers |
Mar 2011 - Present |
|
RF Noise Interference |
May 2009 - Present |
Modulating Boiler Interface Revision 8 |
Mar 2011 - Mar 2011 (Updated March 2011) |