The Mixing Reset Module 421 is designed to operate all of the mechanical equipment in a hydronic heating system, except for zones, coordinating their operation through network communication. It can be used in applications ranging from a single zone of mixed radiant with an on/off boiler to multiple radiant floor zones with an on/off boiler. This control regulates one mixed heating water temperature through Outdoor Temperature Reset and Indoor Temperature Feedback. It is capable of controlling a single on/off boiler, floating action or variable speed injection mixing, and can expand up to 24 zones in total.
Automatic Boiler Differential
Boiler Protection
Exercising
Expandable up to 24 zones
Indoor Temperature Feedback
One touch overrides (with optional User Switch)
Outdoor Temperature Reset
Powered pump outputs
Single on /off boiler control
System setback (with optional timer)
Variable speed, or floating action mixing control
Warm Weather Shut Down
Zone Synchronization
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 1.6 lb (730 g) |
| Dimensions | 3-5/8" H x 5-3/8" W x 9/16" D (92 x 137 x 14 mm) |
| Approvals | CSA C US, meets Class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤80% to 88°F (31°C), down to 50% above 104°F (40°C), Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree |
| Power supply | Provided by interconnected tekmarNet Zone Manager |
| Pump relays | 115 V (ac) 5 A, 1/6 hp |
| Variable pump | 115 V (ac) 2.5 A, fuse T2.5 A 250 V |
| Combined load | 7.5 A max (System and Variable Speed Pump) |
| Floating action output | 24 V (ac) 8 VA max |
| Demands | 20 to 260 V (ac) / 0.1 VA @ 24 V |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070 and 2 of Universal Sensor 082 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Aug 2007 - Present |
|
|
Job Record |
Aug 2009 - Present |
|
|
Wiring Brochure |
Mar 2009 - Present |
|
Installation & Operation Manual |
Jun 2005 - Aug 2007 (For pre 08/07 models) |
|
|
Wiring Brochure |
Aug 2007 - Dec 2008 |
RF Noise Interference |
May 2009 - Present |

tN4 Zone Manager
335

tN4 Zone Manager
336

tN4 Dual Zone Manager
337

tN4 Gateway
482

tN4 Gateway
483

3-Way Mixing Valve
710

3-Way Mixing Valve
711

3-Way Mixing Valve
712

3-Way Mixing Valve
713

3-Way Mixing Valve
714

4-Way Mixing Valve
720

4-Way Mixing Valve
721

4-Way Mixing Valve
722

4-Way Mixing Valve
723

4-Way Mixing Valve
724

Actuating Motor
741