The Boiler Control 275 is designed to stage up to four condensing or non-condensing, modulating or on-off boilers using P.I.D. staging to accurately maintain temperature. Water temperature is controlled by Outdoor Temperature Reset for space heating applications or a fixed setpoint for Domestic Hot Water (DHW) tank heating or industrial process heating applications. The control will also accept an analog 0-10 V (dc) signal from an Energy Management System (EMS) to control the water temperature. Boiler Equal Run Time Rotation, pump exercising and stand-by system pump operation increase boiler plant reliability. The control is tekmarNet® communication compatible allowing for internet connectivity using an optional Gateway 483.
Access levels
Alerts
Automatic Boiler Differential
Boiler pump(s) operation (optional)
Condensing & non-condensing boiler groups
Control up to 4 modulating or on/off boilers
DHW Priority (optional)
DHW pump operation
Equal Run Time Rotation
Exercising
Outdoor Temperature Reset
Powered system pump output
Primary pump sequencing
Programmable Schedule
Test sequence to ensure proper component operation
Warm Weather Shut Down
tekmarNet® 4 Compatible
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 3.3 lb. (1500 g) |
| Dimensions | 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) |
| Enclosure | Blue PVC plastic, NEMA type 1 |
| Approvals | CSA C US, meets class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Non-condensing |
| Power supply | 115 V (ac) ±10%, 60 Hz, 7 VA, 1150 VA max |
| Relays | 230 V (ac) 5 A, 1/3 hp |
| Modulating Output | 0 - 10 V (dc), Minimum 2500 ohms |
| Demands | 20 to 260 V (ac) 2 VA |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | Outdoor Sensor 070, 2 of Universal Sensor 082, and 500 ohm Resistor |
| -Optional | tekmar type: 071, 078, 082 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2012 - Present |
|
|
Installation & Operation Manual |
Nov 2012 - Present |
Application Brochure |
Nov 2012 - Current |
More advanced application drawings can be found in our Solutions section.
Installing the 275 Modulating Boiler Control with Modulating Boilers |
Mar 2011 - Present |
|
RF Noise Interference |
May 2009 - Present |
Modulating Boiler Interface Revision 8 |
Mar 2011 - Mar 2011 (Updated March 2011) |