The tekmarNet® 4 Thermostat 542 is designed to operate mechanical equipment to deliver heat to a single zone within a hydronic heating system while maintaining a programmable setback schedule. It can be used with any terminal unit type, including radiant floor, baseboard, and fan coils. It is capable of controlling a zone valve or zone pump directly or through a tekmarNet® 4 Wiring Center or Zone Manager to maintain air temperature and an auxiliary temperature. This temperature is typically floor, but could also be remote air.
2 Auxiliary Sensor inputs
Auto Heating Cycle
Backlight
CSA C US approved for use in USA and Canada
Cool Group member
Exercising
Freeze Protection
One touch overrides (with optional User Switch)
Outdoor temperature display
Programmable setback schedule
Pulse Width Modulation
Room Temperature Limiting
Schedule master
Zone Post Purge
Zone Synchronization
tekmarNet® 4 communication compatible
| Control | Microprocessor control. This is not a safety (limit) control |
| Packaged weight | 0.5 lb. (230 g) |
| Dimensions | 2-7/8" H x 2-7/8" W x 13/16" D (73 x 73 x 21 mm) |
| Enclosure | White PVC plastic, NEMA type 2 |
| Approvals | CSA C US, meets Class B: ICES & FCC Part 15 |
| Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤80% to 88°F (31°C), down to 50% above 104°F (40°C), Altitude <6560 ft. (2000 m), Installation Category II, Pollution Degree |
| Power supply | 24 V (ac) ± 10%, 60 Hz, 1.6 VA |
| W1 relay | 24 V (ac) 2 A max |
| Sensors | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
| -Included | None |
| -Optional | tekmar type # 070, 071, 072, 073, 076, 077, 078, 079, 082, 084 |
| Warranty | Limited 3 Year Warranty |
In most cases the current version of literature will work, otherwise use the piece of literature most closely matching the date code of your product.
|
Product Submittal |
Jan 2011 - Present |
|
|
Installation & Operation Manual |
Aug 2007 - Present |
|
|
User Manual |
Aug 2007 - Present |
|
Job Record |
Aug 2009 - Present |
|
|
User Manual |
Jun 2005 - Aug 2007 |
|
|
Wiring Brochure |
Dec 2008 - Present |
RF Noise Interference |
May 2009 - Present |